HOT WATER/GASMULTIPLE ANDCASCADING BOILERSAPPLICATION GUIDEPrinted in the U.S.A. 711 Publication No. CJ-10-HWGwww.slantfin.comGuidelines for the des
Jaguar Caravan Multiple and Cascading Boilers10Figure 5.
Jaguar Caravan Multiple and Cascading Boilers 11Figure 6. Alternative multiple side wall air intake & exhaust venting.Note:• Air intake opening mu
Jaguar Caravan Multiple and Cascading Boilers12Figure 7.
Jaguar Caravan Multiple and Cascading Boilers 13Figure 8. Direct Venting and Air Intake Through a Roof.** Knowledge of local conditions will reveal th
Jaguar Caravan Multiple and Cascading Boilers147. CONDENSATE REMOVAL SYSTEMThe Jaguar J-390C boiler is equipped with a built-in condensationdrain and
Jaguar Caravan Multiple and Cascading Boilers 15Figure 10. shows typical field piped primary loops for Jaguar Multiple boiler systems. Each Jaguar bo
Jaguar Caravan Multiple and Cascading Boilers16Figure 11. shows water primary piping using Slant/Fin headers. Each Jaguar boiler shall be installed wi
Jaguar Caravan Multiple and Cascading Boilers17GAS PIPINGThis section contains sizing and construction recommendationsfor fuel supply piping to Carava
Jaguar Caravan Multiple and Cascading Boilers18FROMHEADER3 1/4”TYPFigure 12.Typical gas supply installation for Jaguar boiler.NominalIron PipeSize Inc
Jaguar Caravan Multiple and Cascading Boilers 19JAGUAR MULTIPLE BOILER SYSTEM CONTROLThe two common control methods for Jaguar MultipleBoiler Systems
Jaguar Caravan Multiple and Cascading Boilers21. INTRODUCTIONIf additional information is desired please contact your localSlant/Fin Sales Representat
Jaguar Caravan Multiple and Cascading Boilers20Maximum of 8 boilers could be set up for cascading. See page 3 forpiping instruction. A water supply sy
Jaguar Caravan Multiple and Cascading Boilers 21Figure 14.
Jaguar Caravan Multiple and Cascading Boilers22Figure 15.
Jaguar Caravan Multiple and Cascading Boilers 2310.2 SET DISPLAYSSet the switch on the rear of the displays as follows:Master Boiler: ON (Down Posit
Jaguar Caravan Multiple and Cascading Boilers24MODE DISPLAYDESCRIPTIONChanging space heating post pump time. Settable from 10 to 900 seconds.(steps of
Jaguar Caravan Multiple and Cascading Boilers 257070 60 -20-10 -3001020304050Outdoor Temp. (°F)WaterSupplyTarget Temp.(°F)185 °F1401501301901801701601
Jaguar Caravan Multiple and Cascading Boilers2610.7 CHANGING SYSTEM WATER TEMPERATURESetting system supply water temperature for space heating(see tab
Jaguar Caravan Multiple and Cascading Boilers 27MODE DISPLAY DESCRIPTION & TEMPERATURE DISPLAYNO FUNCTIONNO FUNCTIONNO FUNCTIONTemperature display
Jaguar Caravan Multiple and Cascading Boilers28MODE DISPLAY DESCRIPTION & TEMPERATURE DISPLAYFollower boiler is on stand-by mode.Temperature displ
Jaguar Caravan Multiple and Cascading Boilers 29An external control with 0-10 Vdc output such as Tekmar 265 or 275could be used to operate up to 4 boi
Jaguar Caravan Multiple and Cascading Boilers 3‘’‘’‘’‘’ ‘’‘’‘’‘’‘’‘’‘’‘’‘’‘’‘’‘’‘’‘’‘’‘’‘’‘’** “L” Dimensions and spacing between boilers are for Slan
Jaguar Caravan Multiple and Cascading Boilers30J5J8J1SWITCH (MUST BE ON"OFF"POSITION)9 10 11 12 13 14 BOILER TERMINALSWHITEBLACKNOTE: FOR EA
Jaguar Caravan Multiple and Cascading Boilers 31MODE DISPLAY DESCRIPTION & TEMPERATURE DISPLAYNO FUNCTIONNO FUNCTIONNO FUNCTIONTemperature display
Jaguar Caravan Multiple and Cascading Boilers32LOCKOUT ERRORS: Indicated by an “A” in the mode display. The reset button must be pressed to clear the
Jaguar Caravan Multiple and Cascading Boilers 33BLOCKING ERRORS: Indicated by an “E” in the mode display. Operation is automatically restored, once th
Jaguar Caravan Multiple and Cascading Boilers34ERROR CODE INDICATION REMEDY30Excess Flue TemperatureCheck flue gas temperature, at the maximum firing
Jaguar Caravan Multiple and Cascading Boilers 35A “Hybrid Condensing/Non-Condensing Boiler System” isa combination of condensing and non-condensing bo
SLANT/FIN CORPORATION, Greenvale, N.Y. 11548 • Phone: (516) 484-2600FAX: (516) 484-5921 • Canada: Slant/Fin LTD/LTEE, Mississauga, Ontariowww.slantfin
Jaguar Caravan Multiple and Cascading Boilers4SAFETYKEEP THE BOILER AREA CLEAR AND FREE FROMCOMBUSTIBLE MATERIALS, GASOLINE AND OTHERFLAMMABLE VAPORS
Jaguar Caravan Multiple and Cascading Boilers 5Figure 2. Typical layout of 3 Jaguar Boilers using Slant/Fin Headers (Minimum Clearance)
Jaguar Caravan Multiple and Cascading Boilers64. FRESH AIR AND CONTAMINATION PREVENTIONThe combustion air supply must not be susceptible to contamina-
Jaguar Caravan Multiple and Cascading Boilers 76. VENTING REQUIREMENTSThe Jaguar J-390C is a sealed combustion type boiler, it may beinstalled and ven
Jaguar Caravan Multiple and Cascading Boilers8VENT AND AIR INTAKE RESTRICTIONS1. Maximum allowed equivalent vent and air intake length for all of the
Jaguar Caravan Multiple and Cascading Boilers 9Wall opening for Slant/Finvent air intake terminationHeight - 5 3/4"Width - 12 3/4”Wall thickness